Sign In | Join Free | My lightneasy.org
lightneasy.org
Products
Search by Category
Home > Other Machinery & Industry Equipment >

Electronic Automatic Transformer Testing Equipment On Load Tap Change Tester

Categories Transformer Testing Equipment
Brand Name: GDZX
Model Number: ZXYZ-2000
Place of Origin: Hubei, China
MOQ: 1 Set
Price: $1,500.00 - $4,500.00 / Sets
Payment Terms: L/C, D/A, D/P, T/T
Supply Ability: 100 Set/Sets per Month
Delivery Time: 7~10 work days
Packaging Details: Carton or wooden box
Product name: Automatic Transformer On Load Tap Change Tester
Output current: 1.0A, 0.5A, 0.3A gears
Operating temperature: -20 ℃ ~ +50 ℃
Environmental humidity: ≤ 90% RH
Power supply: AC220V ± 10%, 50Hz ± 10%
Power: Electronic
  • Haven't found right suppliers
  • Our buyer assistants can help you find the most suitable, 100% reliable suppliers from China.
  • And this service is free of charge.
  • we have buyer assistants who speak English, French, Spanish......and we are ready to help you anytime!
Submit Buying Request
  • Product Details
  • Company Profile

Electronic Automatic Transformer Testing Equipment On Load Tap Change Tester

This tester is mainly used to measure the transformer on-load tap-changer transition waveform, transition time, the instantaneous transition resistance, three-phase synchronization and so on.

The instrument features highly intelligent, English menu prompts, simple operation. Instrument small size, light weight, strong anti-interference ability. It is ideal instrument to ensure safe production and good quality in power plants units, transformer manufacturing industry.

Features

1. Large output current, light weight.

2. Open circuit voltage 28V, 1A gear for testing 10Ω transition resistance, 0.5A, 0.3A for larger transition resistance.

3. Perfect protection circuit, reliable to use.

4. Vertical chassis structure, 5.7-inch large LCD display, easy site operation.

5. U disk storage function

Parameters

Output current1.0A, 0.5A, 0.3A gears
Resistance range1.0A: 0.1 ~ 10Ω; 0.5A: 5 ~ 20Ω; 0.3A: 10 ~ 40Ω
Resistance measurement accuracy± (reading × 5% + 5 words), resolution: 0.01Ω
Transition time measurement range1 ~ 250mS
Transition time measurement accuracy± 1mS, resolution: 0.1mS
Sampling frequency10K
StorageU disk storage, local storage
Operating temperature-20 ℃ ~ +50 ℃
Environmental humidity≤ 90% RH, no condensation
Working power

AC220V ± 10%, 50Hz ± 10%


Quality Electronic Automatic Transformer Testing Equipment On Load Tap Change Tester for sale