Sign In | Join Free | My lightneasy.org
lightneasy.org
Products
Search by Category
Home > Pressure Measuring Instruments >

New original power factor controller SCHNEIDER VPL12N is in stock.

Categories Programmable Logic Controller
Delivery Time: in stock
Model Number: VPL12N
Place of Origin: Germany
Price: USD$520
Packaging Details: original packing
Supply Ability: 10PC
Payment Terms: L/C, D/A, D/P, T/T, Western Union
MOQ: 2
Brand Name: SCHNEIDER
  • Haven't found right suppliers
  • Our buyer assistants can help you find the most suitable, 100% reliable suppliers from China.
  • And this service is free of charge.
  • we have buyer assistants who speak English, French, Spanish......and we are ready to help you anytime!
Submit Buying Request
  • Product Details
  • Company Profile

New original power factor controller SCHNEIDER VPL12N is in stock.


Specifications

Main
RangePowerLogic
Product namePowerLogic PFC Controller
Product or Component TypePower factor controller
Device short nameVPL12
Complementary
Number of step output contacts12
[Us] rated supply voltage90...550 V AC
<= 999 kV AC with external VT
Measurement current0…5 A
Measurement voltage90…550 V AC 50/60 Hz
Operating ModeManual or automatic
Number of quadrant operation for generator application4
Device connectionCommunication Modbus RS485
Input functionSwitch 1 x dry contact
Colour codeFront dark grey RAL 7016
Display TypeBacklit LCD
Display size56 x 25 mm
Function AvailableManual programming
Automatic initialisation
Automatic detection
Advanced programming (expert)
Any step sequence
Metering typePower factor and displacement PF (signed, four quadrant)
Total current harmonic distortion THD (I)
Power factor average over lifetime
Temperature maximum
Phase current I1, I2, I3 RMS on load
Active power P, P1, P2, P3 on load
Reactive power Q, Q1, Q2, Q3 on load
Apparent power S, S1, S2, S3 on load
Voltage U21, U32, U13, V1, V2, V3 on load
Type of MeasurementCapacitor current overload Irms/I1
Individual voltage harmonic
Power factor
Operating time
Cos φ
Ambient temperature inside the cubicle
Tan φ
Information DisplayedNumber of switching cycles per step
Individual step size in kVAr
Remaining step capacity in %
Type of alarmsStep power loss < 75 %)message and alarm contact + step blocked
Step faultymessage and alarm contact + step blocked
High current > 6 A CT)message and alarm contact
Hunting (unstable regulation)message and alarm contact + step blocked
Low current < 15 mA CT)message and alarm contact
Overcompensationmessage and alarm contact
Capacitor current overload (Irms/I1) > 130 % I1)message and alarm contact + step switched off
Over Temperature 50 °C)message and alarm contact + step switched off
Over Temperature 30 °C)fan switch
Over Voltage +/- 10 %)message and alarm contact + control stopped
Total harmonic distortion > 7 %)message and alarm contact + step switched off
Data recording5 alarms
Operational Hours alarm100000 h without maintenance
Operational counter alarm65000 cycles without maintenance
Input typePhase to phase
Phase to neutral
Insensitive to CT polarity
Insensitive to phase rotation polarity
Current input CT...X/5 A and X/1 A
Output typeControl relay 0.2 A 110 V DC
Control relay 1 A 48 V DC
Control relay 2 A 400 V AC 50/60 Hz
Control relay 1 A 24 V DC
Control relay 5 A 250 V AC 50/60 Hz
Control relay 5 A 120 V AC 50/60 Hz
Fan 5 A 250 V AC 50/60 Hz
Fan 1 A 48 V DC
Alarm relay 5 A 250 V AC 50/60 Hz
Alarm relay 1 A 48 V DC
Maximum at the common terminal10 A
Settings operating modeAutomatic
Manual
Type of settingChoice of stepping programs auto
Choice of stepping programs LIFO
Choice of stepping programs linear
Delay between 2 successive switch on the same step 5...1200 s
Step configuration programming auto
Step configuration programming off
Step configuration programming fixed
Target cos phi 0.7 inductive...0.7 capacitive
Target cos phi dual cos φ
Measurement accuracyVoltage +/- 1 %
Current +/- 1 %
Frequency +/- 1 %
Energy (P,Q,S) +/- 2 %
Cos φ +/- 2 %
Total voltage harmonic distortion THD (U) +/- 2 %
Individual voltage harmonic +/- 3 %
Temperature +/- 3 °C
Time delay range1...6500 s on reconnection)
1...6500 s on response)
Provided EquipmentUser Manual
Mounting ModeFlush-mounted
Mounting supportPanel 0.04…0.1 in (1…3 mm)
Mounting LocationIn cabinet
Cut-out dimensions138 x 138 mm
Height5.7 in (144 mm)
Width5.7 in (144 mm)
Depth2.3 in (58 mm)
Product Weight1.3 lb(US) (0.6 kg)
Compatibility codeVPL 12
Environment
StandardsIEC 61000-6-4
UL 61010-1
EN 61010-1
IEC 61000-6-2
IEC 61326-1
Product CertificationsEAC
NRTL
cNRTL
CE
IP degree of protectionFront face IP41
Rear face IP20
Operating altitude<= 6561.68 ft (2000 m)
Ambient Air Temperature for Operation-4…140 °F (-20…60 °C)
Ambient Air Temperature for Storage-40…185 °F (-40…85 °C)
Ordering and shipping details
CategoryUS1DE2C00050
Discount ScheduleDE2C
GTIN3606480800115
ReturnabilityYes
Country of originDE
Packing Units
Unit Type of Package 1PCE
Nbr. of units in pkg.1
Package 1 Height3.622 in (9.200 cm)
Package 1 Width6.969 in (17.700 cm)
Package 1 Length7.244 in (18.400 cm)
Package weight(Lbs)25.644 oz (727.000 g)
Unit Type of Package 2S03
Number of Units in Package 28
Package 2 Height11.811 in (30.000 cm)
Package 2 Width11.811 in (30.000 cm)
Package 2 Length15.748 in (40.000 cm)
Package 2 Weight13.569 lb(US) (6.155 kg)
Unit Type of Package 3P06
Number of Units in Package 364
Package 3 Height29.528 in (75.000 cm)
Package 3 Width23.622 in (60.000 cm)
Package 3 Length31.496 in (80.000 cm)
Package 3 Weight128.768 lb(US) (58.408 kg)
Quality New original power factor controller SCHNEIDER VPL12N is in stock. for sale
Send your message to this supplier
 
*From:
*To: Mengchuan Instrument Co,Ltd.
*Subject:
*Message:
Characters Remaining: (0/3000)
 
Inquiry Cart 0